Skip to main content

Designing of the PV system

What is a solar PV system?

Solar photovoltaic system or Solar power system is one of renewable energy system which uses PV modules to convert sunlight into electricity. The electricity generated can be either stored or used directly, fed back into grid line or combined with one or more other electricity generators or more renewable energy source. The solar PV system is a very reliable and clean source of electricity that can suit a wide range of applications such as residence, industry, agriculture, livestock, etc.


Major system components:

Solar PV system includes different components that should be selected according to your system type, site location, and applications. The major components for the solar PV system are solar charge controller, inverter, battery bank, auxiliary energy sources and loads (appliances).

  1.   PV module - converts sunlight into DC electricity.
  2.  The solar charge controller - regulates the voltage and current coming from the PV  panels going to battery and prevents battery overcharging and prolongs the battery life.
  3.  An inverter - converts DC output of PV panels or wind turbine into a clean AC current for AC appliances or fed back into grid line.
  4.  Battery - stores energy for supplying to electrical appliances when there is a demand.
  5.  Load - is electrical appliances that connected to solar PV system such as lights, radio, TV, computer, refrigerator, etc. 
  6.  Auxiliary energy sources - is diesel generator or other renewable energy sources.

Solar PV system sizing

1. Determine power consumption demands
The first step in designing a solar PV system is to find out the total power and energy consumption of all loads that need to be supplied by the solar PV system as follows:
     1.1 Calculate total Watt-hours per day for each appliance used.
           Add the Watt-hours needed for all appliances together to get the total Watt-hours per day which
           must be delivered to the appliances.

     1.2 Calculate total Watt-hours per day needed from the PV modules.
            Multiply the total appliances Watt-hours per day times 1.3 (the energy lost in the system) to get the total Watt-hours per day which must be provided by the panels.
2. Size the PV modules

Different size of PV modules will produce a different amount of power. To find out the sizing of PV module, the total peak watt produced needs. The peak watt (Wp) produced depends on the size of the PV module and climate of site location. We have to consider the panel generation factor which is different in each site location. For Thailand, the panel generation factor is 3.43. To determine the sizing of PV modules, calculate as follows:

     2.1 Calculate the total Watt-peak rating needed for PV modules
           Divide the total Watt-hours per day needed from the PV modules (from item 1.2) by 3.43 to get the total Watt-peak rating needed for the PV panels needed to operate the appliances.
     2.2 Calculate the number of PV panels for the system
           Divide the answer obtained in item 2.1 by the rated output Watt-peak of the PV modules available to you. Increase any fractional part of the result to the next highest full number and that will be the a number of PV modules required Result of the calculation is the minimum number of PV panels. If more PV modules are installed, the system will perform better and battery life will be improved. If fewer PV modules are used, the system may not work at all during cloudy periods and battery life will be shortened.

3. Inverter sizing

An inverter is used in the system where AC power output is needed. The input rating of the inverter should never be lower than the total watt of appliances. The inverter must have the same nominal voltage as your battery.
For stand-alone systems, the inverter must be large enough to handle the total amount of Watts you will be using at one time. The inverter size should be 25-30% bigger than the total Watts of appliances. In case of the appliance, a type is a motor or compressor then inverter size should be minimum 3 times the capacity of those appliances and must be added to the inverter capacity to handle surge current during starting.
For grid-tied systems or grid-connected systems, the input rating of the inverter should be same as PV array rating to allow for safe and efficient operation.

4. Battery sizing

The battery type recommended for using in a solar PV system is a deep cycle battery. Deep cycle battery is specifically designed for to be discharged to low energy level and rapid recharged or cycle charged and discharged day after day for years. The battery should be large enough to store sufficient energy to operate the appliances at night and cloudy days. To find out the size of the battery, calculate as follows:

     4.1 Calculate total Watt-hours per day used by appliances.
     4.2 Divide the total Watt-hours per day used by 0.85 for battery loss.
     4.3 Divide the answer obtained in item 4.2 by 0.6 for the depth of discharge.
     4.4 Divide the answer obtained in item 4.3 by the nominal battery voltage.
     4.5 Multiply the answer obtained in item 4.4 with days of autonomy (the number of days that you

           need the system to operate when there is no power produced by PV panels) to get the required
           Ampere-hour capacity of the deep-cycle battery.
Battery Capacity (Ah) = Total Watt-hours per day used by appliances x Days of autonomy
(0.85 x 0.6 x nominal battery voltage)
5. Solar charge controller sizing

The solar charge controller is typically rated against Amperage and Voltage capacities. Select the solar charge controller to match the voltage of the PV array and batteries and then identify which type of solar charge controller is right for your application. Make sure that the solar charge controller has enough capacity to handle the current from the PV array.
For the series charge controller type, the sizing of the controller depends on the total PV input current which is delivered to the controller and also depends on PV panel configuration (series or parallel configuration).
According to standard practice, the sizing of the solar charge controller is to take the short circuit current (Isc) of the PV array and multiply it by 1.3
Solar charge controller rating = Total short circuit current of PV array x 1.3
Remark: For MPPT charge controller sizing will be different. (See Basics of MPPT Charge Controller)
Example: A house has the following electrical appliance usage:
  • One 18 Watt fluorescent lamp with electronic ballast used 4 hours per day.
  • One 60 Watt fan used for 2 hours per day.
  • One 75 Watt refrigerator that runs 24 hours per day with a compressor run 12 hours and off 12 hours.
The system will be powered by 12 Vdc, 110 Wp PV module.

1. Determine power consumption demands

Total appliance use = (18 W x 4 hours) + (60 W x 2 hours) + (75 W x 24 x 0.5 hours)
= 1,092 Wh/day
Total PV panels energy needed = 1,092 x 1.3
= 1,419.6 Wh/day.

2. Size the PV panel

2.1 Total Wp of PV panel capacity needed= 1,419.6 / 3.4
= 413.9 Wp
2.2  Number of PV panels needed= 413.9 / 110
= 3.76 modules
                                                            
          Actual requirement = 4 modules
          So this system should be powered by at least 4 modules of 110 Wp PV module.

3. Inverter sizing

    Total Watt of all appliances = 18 + 60 + 75 = 153 W
    For safety, the inverter should be considered 25-30% bigger size. 
    The inverter size should be about 190 W or greater.

4. Battery sizing

    Total appliances use = (18 W x 4 hours) + (60 W x 2 hours) + (75 W x 12 hours)
    Nominal battery voltage = 12 V
    Days of autonomy = 3 days
    Battery capacity = [(18 W x 4 hours) + (60 W x 2 hours) + (75 W x 12 hours)] x 3
                                                (0.85 x 0.6 x 12)
    Total Ampere-hours required 535.29 Ah
    So the battery should be rated 12 V 600 Ah for 3-day autonomy.

5. Solar charge controller sizing

    PV module specification
    Pm = 110 Wp
    Vm = 16.7 Vdc
    Im = 6.6 A
    Voc = 20.7 A
    Isc = 7.5 A
    Solar charge controller rating = (4 strings x 7.5 A) x 1.3 = 39 A
    So the solar charge controller should be rated 40 A at 12 V or greater.

If anyone has needed help regarding the designing of the PV system then leave the comments below.

Comments

  1. This comment has been removed by the author.

    ReplyDelete
  2. This comment has been removed by the author.

    ReplyDelete

Post a Comment

Popular posts from this blog

Electronic Engineer at Thinture Technologies Pvt. Ltd

Hello Dear Readers, Currently, at Thinture Technologies Pvt. Ltd vacancy for Electronic Engineer role. Thinture Technologies Pvt. Ltd. is a vehicle control systems manufacturer, with a primary focus on road speed limitation and GPS-based tracking systems. All of our products are designed in-house from basic circuit designing to firmware, algorithm to PCB designing, online software platforms to mechanical assembly drawings, and standard operating procedures for aftermarket usage. Role Description: This is a full-time on-site role for an Electronic Engineer located in Bengaluru. The Electronic Engineer will be responsible for the day-to-day tasks associated with electronic engineering, including electronics, electrical engineering, circuit design, testing, and more. Qualifications: Strong electronic engineering skills Sound knowledge of circuit design and electrical engineering Experience with electronics testing and quality assurance Proficient in using software tools for schematic capt

R&D Intern (Electronics Engineering) at Greaves Electric Mobility

Hello Dear Readers, Currently, at Greaves Electric Mobility vacancy for an R&D Intern (Electronics Engineering) role. At Greaves Electric Mobility, we build products and solutions that are designed to democratize smart and sustainable mobility and do our bit to heal the Planet. Backed by the 164 year engineering legacy of Greaves, our portfolio of electric two and three wheelers are made in India at manufacturing sites across Tamil Nadu, Telangana and Uttar Pradesh. Key Responsibilities: Collaborate with experienced engineers in the research and development of electric mobility technologies. Participate in the design, prototyping, and testing of electronic and electrical systems for electric vehicles. Contribute to the analysis and improvement of automotive electrical systems, ensuring compliance with industry standards. Assist in troubleshooting and problem-solving activities related to electric vehicle components. Stay updated on the latest advancements in the electric mobility s

Hardware Design Engineer at TSC Tech Labs

  Hello Dear Readers, Currently, at TSC Tech Labs  vacancy for a Hardware Design Engineer role. Company Description: TSC Tech Labs is a Space and Defence Startup based in Bengaluru. The company has a legacy of developing three Satellites with Space Heritage and holds five active Defence Contracts with the Indian Navy. Role Description: This is a Senior Hardware Design Engineer role and is a full-time on-site position located in Bengaluru. The Senior Hardware Design Engineer will be responsible for designing and developing electronics hardware, circuit design, hardware architecture and hardware development for satellite and defense systems. Responsibilities: Review and understand electrical schematic designs Perform design reviews with other team members Perform layout design based on these schematic designs, complying with product requirements Close collaboration with other project members (system, mechanical, hardware, and firmware engineers, etc.) Prepare PCB/PCBA production document